OWNERS SERVICE MANUAL
NO. 05618
INSTALLATION, OPERATING & SERVICING
INSTRUCTIONS
for
AMEREX
CARBON DIOXIDE
MODEL 333 50 POUND WHEELED
MODEL 334 100 POUND WHEELED
MODEL 335 100 POUND STATIONARY
* * * RECHARGE FIRE EXTINGUISHERS IMMEDIATELY AFTER ANY USE * * *
All fire extinguishers should be installed, inspected and maintained in accordance with the National Fire
Protection Association standard titled "Portable Fire Extinguishers", NFPA-10 and the requirements of local
authorities having jurisdiction.
When maintenance is indicated it should be performed by trained persons having proper equipment. Fire
extinguishers are pressure vessels and must be treated with respect and handled with care. They are mechanical
devices and require periodic maintenance to be sure that they are ready to operate properly and safely. Amerex
strongly recommends that the maintenance of portable fire extinguishers be done by a trained professional your
local authorized Amerex Distributor.
Amerex Corporation makes original factory parts available to insure proper maintenance use of substitute parts
releases Amerex of its warranty obligations. Amerex parts have machined surfaces and threads that are
manufactured to exacting tolerances. O-rings, hoses, nozzles, and all metal parts meet precise specifications and
are subjected to multiple in-house inspections and tests for acceptability. There are substitute parts available that
are incorrectly labeled as UL component parts, some are advertised as Amerex type. None of these meet UL
requirements and all of them voids the Amerex extinguisher warranty and UL listing. DO NOT SUBSTITUTE.
AMEREX CORPORATION P.O. BOX 81 TRUSSVILLE, ALABAMA 35173-0081
Phone: 205/655-3271 Fax: 800/654-5980
e-mail: [email protected] Web Page: http://www.amerex-fire.com
Printed in U.S.A.
0M05618 Rev 9/05
REFERENCES IN THIS MANUAL: AVAILABLE FROM:
NFPA-10 Portable Fire Extinguishers National Fire Protection Association
1 Batterymarch Park, P. O, Box 9101
Quincy, MA 02269-9101
CGA C-1 Methods for Hydrostatic Testing of Compressed Gas Association, Inc.
Compressed Gas Cylinders 4221 Walney Road, 5
th
Floor
CGA C-6 Standard for Visual Inspection of Chantilly, VA 20151-2923
Compressed Gas Cylinders
Page view 0
1 2 3 4 5 6 7 8

Summary of Contents

Page 1 - 0M05618 Rev 9/05

OWNERS SERVICE MANUAL NO. 05618 INSTALLATION, OPERATING & SERVICING INSTRUCTIONS for AMEREX CARBON DIOXIDE MODEL 333 50 POUND WHEELED MODEL 3

Page 2

1 LIMITED WARRANTY Amerex warrants its fire extinguishers to be free from defects in material and workmanship for a period of six (6) years from the

Page 3 - INSPECTING THE EXTINGUISHER

2 1. Move the extinguisher (wheeled unit) to within approximately 10 feet (50 lb.), 30 feet (100 lb.) of the fire site. 2. Twist and pull ring pi

Page 4 - MAINTENANCE

3 [NFPA-10] A “quick check” should be made of the extinguisher for the following: 1. Located in designated place 2. No obstruction to access or

Page 5

4 tester consisting of a flashlight having an open circuit and a set of two wires with a conductor (clamps or probe) at each end. (NFPA-10 Appendix

Page 6

5 CAUTION: The Models 334 and 335 extinguishers have two 50 lb. cylinders manifolded to a common discharge hose. Properly align the

Page 7 - TROUBLE SHOOTING GUIDE

6 TROUBLE SHOOTING GUIDE WARNING: BEFORE ATTEMPTING TO CORRECT ANY LEAKAGE PROBLEM, BE SURE THAT THE CYLINDER AND HOSE ARE COMPLETELY EMPTY AND DE

Page 8

7 PARTS LIST for 50 and 100 lb. Carbon Dioxide Extinguishers Model 333 - 50 lb. Model 334 – 100 lb. (Two 50 lb. Cylinders) Model 335 – 100 lb. Stati