OWNERS SERVICE MANUAL
NO. 05612
INSTALLATION, OPERATING & SERVICING INSTRUCTIONS
All fire extinguishers should be installed, inspected and maintained in
accordance with the National Fire Protection Association standard
titled "Portable Fire Extinguishers", NFPA-10 and the requirements of
local authorities having jurisdiction.
When maintenance is indicated, it should be performed by trained
persons having proper equipment. Fire extinguishers are pressure
vessels and must be treated with respect and handled with care.
They are mechanical devices and require periodic maintenance to be
sure that they are ready to operate properly and safely. Amerex
strongly recommends that the maintenance of portable fire
extinguishers be done by a trained professional your local
authorized Amerex Distributor.
Amerex Corporation makes original factory parts available to insure
proper maintenance USE OF SUBSTITUTE PARTS RELEASES
AMEREX OF ITS WARRANTY OBLIGATIONS. Amerex parts
have machined surfaces and threads that are manufactured to
exacting tolerances. O-rings, hoses, nozzles, and all metal parts
meet precise specifications and are subjected to multiple in-house
inspections and tests for acceptability. There are substitute parts
available that may be incorrectly labeled as UL component parts,
some are advertised as Amerex type. None of these meet UL
requirements and all of them voids the Amerex extinguisher warranty
and UL listing. DO NOT SUBSTITUTE.
RECHARGE FIRE EXTINGUISHERS IMMEDIATELY AFTER ANY USE
REFERENCES IN THIS MANUAL: AVAILABLE FROM:
NFPA-10 Portable Fire Extinguishers National Fire Protection Association
1 Batterymarch Park, P.O, Box 9101
Quincy, MA 02269-9101
CGA C-1 Methods for Hydrostatic Testing of Compressed Gas Association, Inc.
Compressed Gas Cylinders 4221 Walney Road, 5
th
Floor
CGA C-6 Standard for Visual Inspection of Chantilly, VA 20151-2923
Compressed Gas Cylinders
AMEREX CORPORATION P.O. BOX 81 TRUSSVILLE, ALABAMA 35173-0081
Phone: 205/655-3271 Fax: 800/654-5980
e-mail: [email protected] Web Page: http://www.amerex-fire.com
Printed in U.S.A.
0M05612E Rev. 08/10
STORED PRESSURE, WHEELED & STATIONARY
50 POUND DRY CHEMICAL FIRE EXTINGUISHERS
ABC (AMMONIUM PHOSPHATE BASE), REGULAR
(SODIUM BICARBONATE BASE),
PURPLE K (POTASSIUM BICARBONATE BASE)
Page view 0
1 2 3 4 5 6 ... 10 11

Summary of Contents

Page 1

OWNERS SERVICE MANUAL NO. 05612 INSTALLATION, OPERATING & SERVICING INSTRUCTIONS

Page 2 - EASY REFERENCE

9 Guide to Proper Installation of Hose on 50 lb. Wheeled or Stationary Dry Chemical Fire Extinguishers 1 Connect hose cou

Page 3 - INSTALLATION

10 Item No. Part No. Description Std. Pkg. 1 06018 Valve Asy Complete w/Downtube 1 2 06072 Downtube/Retainer Assembly 1 3 06625 Car

Page 4 - SHUTDOWN

1 INTRODUCTION The Amerex 50 pound Models 495 (ABC), 496 (Regular) & 497 (Purple K) Stored Pressure Wheeled and Models 473 (ABC), 474 (Regu

Page 5

2 PREPARING YOUR NEW EXTINGUISHER FOR USE 1. Examine the extinguisher for evidence of shipping damage. Notify the delivering carr

Page 6

3 OPERATION NOTE: Persons expected to use this extinguisher should be trained in initiating its operation and in the proper fire fighting techniq

Page 7

4 INSPECTING THE EXTINGUISHER PERIODIC INSPECTION PROCEDURES (Monthly or more often if circumstances dictate) [NFPA-10] Periodic inspection of

Page 8 - RECHARGING PROCEDURE

5 4. Check the date of manufacture printed on the extinguisher label (nameplate) or on the agent cylinder dome. The agent cylinder must be hyd

Page 9

6 COMPLETE MAINTENANCE – SIX YEAR TEARDOWN [NFPA-10] Every six years, stored pressure extinguishers that require a 12 year hydrostatic test shall

Page 10

7 11. Check carriage assembly for loose nuts, bolts, frame distortion or damage. Check welds for damage or corrosion. Replace damaged

Page 11

8 8. Install "verification of service" external collar tag. Install discharge valve assembly and attach pressurizing adapter